๐Ÿ‡บ๐Ÿ‡ธ USC
Home & Construction
๐Ÿ”Œ

Voltage Drop Calculator

Check the % drop on a wire run against the 3% limit

๐Ÿ”Œ Circuit details

Distance from the panel to the load (one way). The formula already doubles it for the return conductor.

โœ…

Last updated June 2026

Method: Voltage drop uses Vd = 2 × L × I × R / 1000 for single phase and √3 × L × I × R / 1000 for three phase, with copper resistance per 1000 ft from NEC Chapter 9, Table 8. The 3% / 5% targets follow the NEC informational notes on branch and feeder voltage drop.

Included: Voltage dropped, percent drop, voltage at the load, the 3% pass/fail check, a suggested heavier copper gauge, the maximum run at 3%, and a side-by-side table across all gauges.

Not included: Ampacity and derating checks, aluminum conductors, conduit-fill and temperature corrections, power factor, and harmonic effects. Results are planning estimates, not a code-compliant design.

Voltage drop calculator: everything you need to know

Run AWG 12 copper 100 feet to a 15-amp, 120-volt load and you lose about 5.79 volts along the way - roughly a 4.8% drop, which is over the recommended limit. Step up to AWG 10 and the same run drops only about 3.6 volts (around 3%), and AWG 8 brings it comfortably under. That swing is the whole point of a voltage drop calculator: the wire that is "big enough" to carry the current safely can still deliver too little voltage to the device at the end of a long run. This tool shows the drop in volts, the percent drop, the voltage that actually reaches the load, and whether you are over the 3% line - plus the next copper gauge that fixes it.

How voltage drop is calculated

For a single-phase circuit, the calculator uses the standard formula:

Vd = 2 × L × I × R ÷ 1000

where L is the one-way distance in feet, I is the load current in amps, and R is the conductor resistance in ohms per 1000 feet. The 2 accounts for current traveling out on one conductor and back on the other. For a balanced three-phase circuit, the 2 is replaced by the square root of 3 (about 1.732). The percent drop is simply the volts dropped divided by the system voltage, times 100.

A worked example, step by step

Take a 120 V, 20 A single-phase circuit running 150 feet on AWG 10 copper (R = 1.21 ohms per 1000 ft):

  • Volts dropped: 2 × 150 × 20 × 1.21 ÷ 1000 = 7.26 V.
  • Percent drop: 7.26 ÷ 120 × 100 = 6.05% - well over the 3% target.
  • Voltage at the load: 120 − 7.26 = 112.74 V.

To pass, you would jump to AWG 6 copper (R = 0.491), which drops only about 2.95 V or roughly 2.45%. The calculator runs that same comparison automatically and tells you which gauge to use.

What counts as acceptable voltage drop

The National Electrical Code does not mandate a maximum in most cases, but its informational notes recommend keeping voltage drop to about 3% on a branch circuit and no more than 5% total for the feeder and branch circuit combined. Staying under 3% keeps motors, electronics, lighting and chargers operating at their rated voltage. This calculator uses the 3% branch-circuit figure as its pass/fail threshold.

Why voltage drop matters

Every foot of wire has resistance, and resistance turns electrical energy into heat. On a short run that loss is negligible, but it grows with length and current. The consequences of too much drop include:

  • Wasted energy: the power lost in the wire is heat you pay for but never use.
  • Underperforming equipment: motors lose torque and run hot, heaters and chargers slow down, and pumps move less water.
  • Flicker and failures: LED drivers and sensitive electronics can flicker, reset, or wear out early on a sagging supply.
  • Nuisance trips: motors drawing extra current to compensate can trip breakers or overloads.

How to use this voltage drop calculator

You only need four numbers and a phase selection to get a realistic answer. Work through the fields in order:

  1. System voltage: enter the nominal circuit voltage. Common choices are 120 V and 240 V for homes, and 277 V or 480 V for commercial work - use the quick buttons or type your own.
  2. Load current: enter the running amps of the load (not the breaker size). For motors, use the full-load amps from the nameplate.
  3. One-way distance: measure from the panel to the load along the actual cable route, in feet. Enter the one-way length; the formula doubles it for you.
  4. Wire gauge: pick the copper AWG you plan to use. Smaller numbers mean thicker wire and less drop.
  5. Phase: choose single phase for typical residential circuits, or three phase for balanced three-phase loads.

Press Calculate and read the percent drop at the top. If it is highlighted red, it is over 3%; the calculator names the next gauge that passes and shows a full table so you can see the trade-offs across all sizes.

Who this calculator is for

This tool is built for anyone running a circuit far enough that the wire length matters. That includes:

  • Homeowners and DIYers wiring a detached garage, shed, shop, or backyard outlet.
  • EV-charger installers sizing a 240 V run from the panel to a parking spot.
  • Solar and off-grid builders checking long DC and AC runs between panels, inverters and loads.
  • Pump and irrigation installers feeding a well pump or pivot hundreds of feet away.
  • Apprentices and estimators sanity-checking a design before pulling wire or buying it.

Three common scenarios

Voltage drop problems almost always come down to long runs at meaningful current. Here are three typical cases:

  • Backyard shed, 120 V / 15 A / 120 ft: on AWG 12 the drop is about 5.8% - too much. AWG 8 brings it to roughly 2.3%.
  • EV charger, 240 V / 40 A / 150 ft: on AWG 8 the drop is about 3.8% - over the line; moving to AWG 6 lands near 2.5% and passes.
  • Well pump, 240 V / 10 A / 250 ft: on AWG 10 the drop is about 2.5% - acceptable - but at 350 ft the same wire climbs to roughly 3.5% and exceeds 3%, so distance alone can force an upsize.

Factors that change the result

Adjust the inputs and you will see a handful of factors dominate the outcome:

  • Distance: drop is directly proportional to length - double the run, double the drop.
  • Current: also directly proportional - a heavier load on the same wire drops more voltage.
  • Wire gauge: the biggest lever you control. Each step up in size cuts resistance by roughly 20-37%.
  • System voltage: higher voltage means a smaller percent drop for the same volts lost, which is why 240 V tolerates longer runs than 120 V.
  • Phase: three-phase uses √3 instead of 2, so it shows less line-to-line drop than single phase at the same current.
  • Conductor material and temperature: aluminum and hotter conductors have higher resistance and more drop (this tool assumes copper near 75 degrees C).

Key electrical terms

  • AWG (American Wire Gauge): the U.S. sizing system for wire. Counterintuitively, a smaller number is a thicker wire with lower resistance.
  • Ampacity: the maximum current a conductor can carry safely. It sets the minimum legal wire size before you even consider voltage drop.
  • Resistance (ohms/1000 ft): how much a conductor opposes current per thousand feet. It is the R in the voltage-drop formula.
  • One-way vs. circuit length: one-way is panel-to-load; circuit length is the full out-and-back path. The formula multiplies one-way by 2.
  • Branch circuit vs. feeder: a branch circuit supplies the final loads; a feeder supplies a subpanel. The 3% target is for the branch; 5% is the combined total.
  • Single vs. three phase: single phase is the typical residential supply; three phase is common in commercial and industrial settings and uses the √3 factor.

Tips to keep voltage drop in check

  • Size up one gauge on long runs. If you are near the 3% line, the next size down in AWG number buys a comfortable margin for cheap insurance.
  • Use the higher voltage where you can. A 240 V circuit drops half the percent of a 120 V circuit at the same wattage, so it reaches much farther.
  • Route smart, but don't cheat the math. Measure the real cable path including vertical drops and bends; "as the crow flies" underestimates length.
  • Buy about 10% extra wire. Slack at both ends, splices, and routing around obstacles eat into a spool faster than you expect - order ~10% more than the straight-line estimate.
  • Check ampacity first, then drop. Pick the smallest wire that is legal for the current, then upsize only if the drop is too high.

Limitations and assumptions

This calculator is a fast planning estimate, not a finished design. Keep these assumptions in mind:

  • It assumes copper conductors at about 75 degrees C; aluminum and hotter conductors drop more.
  • It uses simple DC-style resistance and does not model reactance, power factor, or harmonics, which matter on large or inductive loads.
  • It does not check ampacity, derating, conduit fill, or termination temperature limits - all of which can require a larger wire than voltage drop alone.
  • It assumes a balanced load for three-phase and a single steady current, not motor inrush or varying demand.
  • Final sizing must follow the current edition of the National Electrical Code and any local amendments, verified by a licensed electrician for permitted work.

How it compares to related calculators

This page answers "how much voltage will I lose on this run, and is the wire big enough?" If you have a different project question, a sister tool fits better:

  • To estimate concrete for a pad, slab or footing, use the Concrete Calculator.
  • To measure the area of a room or yard, use the Square Footage Calculator.
  • To figure tons or yards of gravel for a base or driveway, use the Gravel Calculator.
  • To size mulch for landscaping beds, use the Mulch Calculator.
  • To convert dimensions of any material into yards, use the Cubic Yard Calculator.
  • To estimate gallons for a paint job, use the Paint Calculator.

โš ๏ธ Common mistakes & edge cases

Entering the round-trip length

The formula already doubles the one-way distance to count the return conductor. If you enter the full out-and-back length, you will overstate the drop by 2x. Enter only panel-to-load distance.

Using the breaker size instead of the load current

Voltage drop depends on the actual running current, not the breaker rating. A 20 A breaker feeding a 9 A load drops voltage based on 9 A. Use the real load (or motor full-load amps), not the overcurrent device.

Checking drop but skipping ampacity

A wire that passes the 3% drop test may still be illegal if it cannot carry the current. Always confirm the conductor's ampacity (with any derating) first, then upsize for voltage drop if needed.

Assuming aluminum behaves like copper

This calculator uses copper resistance. Aluminum has about 60% more resistance per gauge, so the same size will drop noticeably more. For aluminum, size up at least one gauge or use aluminum-specific values.

Note: This calculator gives an estimate, not a code-compliant design. Order about 10% extra wire for slack and splices, and have a licensed electrician verify any permitted work.

❓ Frequently asked questions

How is voltage drop calculated?

For a single-phase circuit, voltage drop is Vd = 2 x L x I x R / 1000, where L is the one-way distance in feet, I is the load current in amps, and R is the conductor resistance in ohms per 1000 ft. The 2 accounts for both the outgoing and return conductors. For a three-phase circuit you replace the 2 with the square root of 3 (about 1.732). Dividing the drop by the system voltage and multiplying by 100 gives the percent drop.

What is an acceptable voltage drop?

The National Electrical Code recommends (in an informational note, not a hard rule) keeping voltage drop to about 3% on a branch circuit, and no more than 5% total for the combined feeder and branch circuit. This calculator flags any result over 3% so you can upsize the wire before it becomes a problem.

Why does voltage drop matter?

Excess voltage drop wastes energy as heat in the wire and starves the load of voltage. Motors run hotter and lose torque, LED drivers can flicker or fail early, heaters and chargers run slowly, and sensitive electronics may misbehave. Long runs to a shed, well pump, EV charger or detached garage are the usual culprits.

Why do I enter the one-way distance instead of the total wire length?

Enter only the distance from the panel to the load. The formula already multiplies by 2 (single phase) to count the return conductor, so you do not double it yourself. If you measured the full round-trip length of wire, enter half of it.

How do I fix excessive voltage drop?

The most common fix is to use a larger conductor (a smaller AWG number has lower resistance). You can also shorten the run if the layout allows, reduce the load on that circuit, or in some cases raise the system voltage. This calculator suggests the next copper gauge that brings the drop back under 3% for your inputs.

Does this work for aluminum wire?

The built-in resistance values are for copper. Aluminum has roughly 60% higher resistance for the same AWG, so an aluminum conductor of the same size will show meaningfully more voltage drop. For aluminum, size up at least one gauge or use published aluminum resistance values and have an electrician verify.

What is the difference between single-phase and three-phase voltage drop?

Single-phase uses a multiplier of 2 (out and back). Three-phase balanced loads use the square root of 3 (about 1.732) because of how the phase currents and voltages combine. For the same current and distance, three-phase shows less line-to-line voltage drop than single-phase.

Does voltage drop affect the wire size I'm allowed to use?

Wire size is set first by ampacity - the conductor must safely carry the load current per NEC tables. Voltage drop is a separate, recommended check on top of that. A wire can be large enough for the current yet still drop too much voltage on a long run, in which case you upsize for the drop, not the ampacity.

What resistance values does this calculator use?

It uses approximate copper conductor resistances in ohms per 1000 ft: AWG 14 = 3.07, 12 = 1.93, 10 = 1.21, 8 = 0.764, 6 = 0.491, 4 = 0.308, 2 = 0.194, and 1/0 = 0.122. These are close to the values in NEC Chapter 9, Table 8 for stranded copper at about 75 degrees C.

Is this calculator a substitute for an electrician or the code?

No. It is a fast planning estimate. Final conductor sizing must satisfy ampacity, temperature, conduit-fill and termination limits, and should follow the current edition of the NEC and any local amendments. For permitted work, have a licensed electrician confirm the design.

๐Ÿ’ก Good to know

Distance and current hit equally hard

Voltage drop is proportional to both the run length and the current. Doubling either one doubles the drop. That is why a modest load 200 feet out can need the same wire as a big load 100 feet out.

Higher voltage reaches farther

At the same wattage, a 240 V circuit carries half the current of a 120 V circuit, so it loses half the percent of voltage on the same wire. Running 240 V where you can is often cheaper than upsizing the conductor.

Buy about 10% extra wire

Slack at the panel and the load, splices, and routing around studs and corners all add length. Order roughly 10% more than your straight-line estimate so you are not splicing a spool that came up short.

Related Calculators